11
: Alarm can be muted by pressing Mute button.
: Alarm can’t be muted by pressing Mute button.
4.3 EPO Operation
EPO Trigger:
In emergency case, The UPS can be power off by activation of the EPO
function by clearing the shortcircuit between the two pin of the EPO
connector or pulling out the EPO connector on right side of the Panel
Interface directly, when the EPO function is active, the Panel Interface
will display as show in table 1 (NO.28).
EPO Cancel:
First of all, Recover shortcircuit wire between the two pin of the EPO
connector then press the OFF button on the UPS panel (not the remote
panel) to cancel the EPO status